|
Ventilation requirements
for houses have traditionally been met on the assumption that the building envelope
is leaky enough that infiltration will suffice. Possible difficulties with this
approach include low ventilation when natural forces (temperature difference and
wind) are weak, unnecessary energy consumption when such forces are strong, drafts
in cold climates, lack of control of ventilation rates to meet changing needs,
potential for interstitial condensation from exfiltration in cold climates, and
lack of opportunity to recover the energy used to condition the ventilation air.
The solution to these concerns is to have a reasonably tight building envelope
and a properly designed and operated mechanical ventilation system.
ASHRAE Standard 62 gives
ventilation rate requirements for houses, essentially 0.35 ACH with at least 8
L/s per occupant. Canadian Standards Association (CSA) Standard F326 expands the
requirements for residential mechanical ventilation systems to cover air distribution
within the house, thermal comfort, minimum temperatures for equipment and ductwork,
system controls, pressurization and depressurization of the dwelling, installation
requirements, and verification of compliance. Verification can be by design or
by test, but the total rate of outside air delivery must be measured.
Mechanical ventilation is
being used in houses, especially in energy-efficient housing demonstration programs.
Possible systems can be characterized as local or central; exhaust, supply, or
balanced; with or without heat recovery; and with continuous, occupant controlled,
or demand controlled (i.e., by pollutant sensing) operation. Note that not all
combinations are viable.
The simplest systems use
bathroom and kitchen fans to augment infiltration. Noise, installed capacity,
lifetime under continuous operation, distribution to all rooms (especially bedrooms),
and energy efficiency issues need to be addressed. Many present bath and kitchen
fans are ineffective ventilators because of poor installation and design. However,
properly specified and installed exhaust fans can form part of good whole-house
ventilation systems and are so specified in some Canadian building codes.
Central exhaust systems
use leakage sites and, in some cases, intentional and controllable openings in
the building envelope as the supply. Such systems are suitable for retrofit in
existing houses. Energy can be recovered from the exhaust air stream with a heat
pump to supplement domestic hot water and/or space heating.
For new houses with tightly
constructed envelopes, balanced ventilation systems with passive heat recovery
(air-to-air heat exchangers or heat recovery ventilators) are appropriate. Fan-induced
supply and exhaust air flows at nearly equal rates over a heat exchanger, where
heat and sometimes moisture is transferred between the airstreams. This reduces
the energy required to condition the ventilation air by typically 60 to 80 %.
It also reduces the thermal comfort problem that occurs when untempered between
streams, biological contamination of wet surfaces, and frosting are concerns associated
with these systems.
|
|